A 2-bus system and corresponding zero sequence network are shown in the figure. The transformers T1 and T2 are connected as


GATE EE · Power Systems
Generate GATE-level questions on Symmetrical and Unsymmetrical faults. Focus on: 1. Symmetrical components and Sequence networks (Positive, Negative, Zero). 2. Symmetrical Three-phase faults. 3. Unsymmetrical faults: Single Line-to-Ground (LG), Line-to-Line (LL), and Double Line-to-Ground (LLG).
41 questions · 20 PYQs · 0 AI practice · GATE EE 2027
A 2-bus system and corresponding zero sequence network are shown in the figure. The transformers T1 and T2 are connected as


A three phase, 100 MVA, 25 kV generator has solidly grounded neutral. The positive, negative, and the zero sequence reactances of the generator are 0.2 pu, 0.2 pu and 0.05 pu, respectively, at the machine base quantities. If a bolted single phase to ground fault occurs at the terminal of the unloaded generator, the fault current in amperes immediately after the fault is_____.
Three-phase to ground fault takes place at locations in the system shown in the figure. If the fault takes place at location , then the voltage and the current at bus A are respectively. If the fault takes place at location , then the voltage and the current at bus A and respectively. The correct statement about voltages and currents during faults at is

For a power system network with n nodes, of its bus impedance matrix is j0.5 per unit. The voltage at node 3 is 1.3 per unit. If a capacitor having reactance of -j3.5 per unit is now added to the network between node 3 and the reference node, the current drawn by the capacitor per unit is
The sequence components of the fault current are as follows : pu, pu, pu. The type of fault in the system is
Two generator units G1 and G2 are connected by 15 kV line with a bus at the mid-point as shown below G1 = 250 MVA, 15kV, positive sequence reactance X = 25% on its own base G2 = 100 MVA, 15kV, positive sequence reactance X = 10 % on its own base =10km, positive sequence reactance X = 0.225 /km In the above system, the three-phase fault MVA at the bus 3 is

The zero-sequence circuit of the three phase transformer shown in the figure


A-3-phase transmission line is shown in figure : Voltage drop across the transmission line is given by the following equation :
Shunt capacitance of the line can be neglect. If the has positive sequence impedance of 15 and zero sequence impedance of 48 , then the values of will be

Consider a power system shown below: Given that: p.u; The positive sequence impedance are p.u and p.u 3-phase Base MVA = 100 voltage base = 400 kV(Line to Line) Nominal system frequency= 50 Hz. The reference voltage for phase 'a' is defined as . A symmetrical three phase fault occurs at centre of the line, i.e. point 'F' at time ' '. The positive sequence impedance from source S1 to point 'F' equals 0.004+j0.04 p.u. The wave form corresponding to phase 'a' fault current from bus X reveals that decaying d.c. offset current is negative and in magnitude at its maximum initial value, Assume that the negative sequence impedances are equal to postive sequence impedance and the zero sequence impedances are three times positive sequence impedances. Instead of the three phase fault, if a single line to ground fault occurs on phase 'a' at point 'F' with zero fault impedance, then the rms of the ac component of fault current ( ) for phase 'a' will be

A three phase balanced star connected voltage source with frequency rad/s is connected to a star connected balanced load which is purely inductive. The instantaneous line currents and phase to neutral voltages are denoted by ( ) and ( ) respectively, and their rms values are denoted by V and I. If
, then the magnitude of R is
Suppose we define a sequence transformation between "a-b-c" and "p-n-o" variables as follows:
where and k and is a constant. Now, if it is given that :
and
then,
Three identical star connected resistors of 1.0 pu are connected to an unbalanced 3-phase supply. The load neutral is isolated. The symmetrical components of the line voltages in pu. are: . If all the pu calculations are with the respective base values, the phase to neutral sequence voltages are
The parameters of a transposed overhead transmission line are given as : Self reactance /km and Mutual reactance /km The positive sequence reactance and zero sequence reactance , respectively in /km are
At a 220 kV substation of a power system, it is given that the three-phase fault level is 4000 MVA and single-line to ground fault level is 5000 MVA Neglecting the resistance and the shunt suspectances of the system. The zero sequence driving point reactance at the bus is
A 3-phase transmission line supplies -connected load Z. The conductor 'c' of the line develops an open circuit fault as shown in figure. The currents in the lines are as shown on the diagram. The positive sequence current component in line 'a' will be

A 500 MVA, 50 Hz, 3-phase turbo-generator produces power at 22 kV. Generator is Y-connected and its neutral is solidly grounded. It sequence reactances are pu and pu.It is operating at rated voltage and disconnected from the rest of the system (no load). The magnitude of the sub-transient line current for single line to ground fault at the generator terminal in pu will be
A 3-phase generator rated at 110 MVA, 11 kV is connected through circuit breakers to a transformer. The generator is having direct axis sub-transient reactance =19%, transient reactance =26% and synchronous reactance =130%. The generator is operating at no load and rated voltage when a three phase short circuit fault occurs between the breakers and the transformer. The magnitude of initial symmetrical rms current in the breakers will be
three-phase alternator generating unbalanced voltages is connected to an unbalanced load through a 3-phase transmission line as shown in figure. The neutral of the alternator and the star point of the load are solidly grounded. The phase voltages of the alternator are , , . The positive sequence component of the load current is

A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive sequence, negative sequence and zero sequence impedances of the alternator are j0.1, j0.1 and j0.04 respectively. The neutral of the alternator is connected to ground through an inductive reactor of j0.05 p.u. The per unit positive, negative and zero sequence impedances of transmission line are j0.1, j0.1 and j0.3, respectively. All per unit values are based on the machine ratings. A solid ground fault occurs at one phase of the far end of the transmission line. The voltage of the alternator neutral with respect to ground during the fault is
A generator is connected to a transformer which feeds another transformer through a short feeder(as shown in figure). The zero sequence impedance values are expressed in pu on a common base and are indicated in figure. The Thevenin equivalent zero sequence impedance at point B is

Want unlimited AI-generated Fault Analysis questions?
Sign up free and practice with adaptive difficulty — Easy, Medium, Hard. New questions every session.
Start practising for free →