GATE EE · Power Systems
Generate GATE-level questions on Voltage control. Focus on: 1. Reactive power compensation: Shunt capacitors/reactors and Series capacitors. 2. Tap-changing transformers and Synchronous condensers. 3. Voltage profile and Power factor improvement.
18 questions · 18 PYQs · 0 AI practice · GATE EE 2027
🎯 These are sample questions
Just sign in to unlock everything. Free for all students.
Consider a distribution feeder, with ratio of 5 . At the receiving end, a 350 kVA load is connected. The maximum voltage drop will occur from the sending end to the receiving end, when the power factor of the load is ___________ (round off to three decimal places).
Consider the two bus power system network with given loads as shown in the figure. All the values shown in the figure are in per unit. The reactive power supplied by generator and are and respectively. The per unit values of , and line reactive power loss ( ) respectively are

A load is supplied by a 230 V, 50 Hz source. The active power P and the reactive power Q consumed by the load are such that and . A capacitor connected across the load for power factor correction generates 1 kVAR reactive power. The worst case power factor after power factor correction is
The inductance and capacitance of a 400 kV, three-phase, 50 Hz lossless transmission line are 1.6 mH/km/phase and 10 nF/km/phase respectively. The sending end voltage is maintained at 400 kV. To maintain a voltage of 400 kV at the receiving end, when the line is delivering 300 MW load, the shunt compensation required is
The complex power consumed by a constant-voltage load is given by ( ), where, and . A compensating shunt capacitor is chosen such that , where Q is the net reactive power consumed by the capacitor load combination. The reactive power (in kVAR) supplied by the capacitor is ____.
Shunt reactors are sometimes used in high voltage transmission systems to
For the system below, are complex power demands at bus 1 and bus 2 respectively. If pu, the VAR rating of the capacitor ( ) connected at bus 2 is

For enhancing the power transmission in along EHV transmission line, the most preferred method is to connect a
Match the items in List-I (To) with the items in the List-II (Use) and select the correct answer using the codes given below the lists.

A loss less transmission line having Surge Impedance Loading (SIL) of 2280 MW is provided with a uniformly distributed series capacitive compensation of 30%. Then, SIL of the compensated transmission line will be
The figure below shows a three phase self-commutated voltage source converter connected to a power system. The converter's dc bus capacitor is marked as C in the figure. The circuit in initially operating in steady state with =0 and the capacitor dc voltage is equal to . You may neglect all losses and harmonics. What action should be taken to increase the capacitor dc voltage slowly to a new steady state value.

A 230 V (Phase), 50 Hz, three-phase, 4-wire, system has a phase sequence ABC. A unity power-factor load of 4 kW is connected between phase A and neutral N. It is desired to achieve zero neutral current through the use of a pure inductor and a pure capacitor in the other two phases. The value of inductor and capacitor is
A 400 V, 50 Hz, three phase balanced source supplies power to a star connected load whose rating is 12 kVA, 0.8 pf (lag). The rating (in kVAR) of the delta connected (capacitive) reactive power bank necessary to bring the pf to unity is
At an industrial sub-station with a 4 MW load, a capacitor of 2 MVAR is installed to maintain the load power factor at 0.97 lagging. If the capacitor goes out of service, the load power factor becomes
A 3-phase 11 kV generator feeds power to a constant power unity power factor load of 100 MW through a 3-phase transmission line. The line-to line voltage at the terminals of the machine is maintained constant at 11 kV. The per unit positive sequence impedance of the line based on 100 MVA and 11 kV is j0.2. The line to line voltage at the load terminals is measured to be less than 11 kV. The total reactive power to be injected at the terminals of the load to increase the line-to-line voltage at the load terminals to 11 kV is
A balanced delta connected load of (8 + j6) per phase is connected to a 400 V, 50 Hz, 3-phase supply lines. If the input power factor is to be improved to 0.9 by connecting a bank of star connected capacitor the required kVAR of the of the bank is
A lossless radial transmission line with surge impedance loading
Consider the model shown in figure of a transmission line with a series capacitor at its mid-point. The maximum voltage on the line is at the location

Want unlimited AI-generated Compensation Techniques And Voltage Profile Control questions?
Sign up free and practice with adaptive difficulty — Easy, Medium, Hard. New questions every session.
Start practising for free →