GATE EE · Electrical Machines
Generate GATE-level questions on Synchronous Machines. Focus on: 1. Cylindrical and Salient pole machines: Performance, Regulation, and Parallel operation. 2. Synchronous Motors: V-curves and inverted V-curves, Starting methods. 3. Power-angle characteristics and Stability.
57 questions · 20 PYQs · 0 AI practice · GATE EE 2027
🎯 These are sample questions
Just sign in to unlock everything. Free for all students.
Instrument(s) required to synchronize an alternator to the grid is/are
The induced emf in a pole, 3-phase star connected synchronous motor is considered to be equal and in phase with the terminal voltage under no load condition. On application of a mechanical load, the induced emf phasor is deflected by an angle of mechanical with respect to the terminal voltage phasor. If the synchronous reactance is , and stator resistance is negligible, then the motor armature current magnitude, in ampere, during loaded condition is closest to, ___________ (round off to two decimal places).
A 3-phase. MVA synchronous generator is connected to an inductive load of power factor via a lossless line with a per-phase inductive reactance of . The per-phase synchronous reactance of the generator is with negligible armature resistance. If the generator is producing the rated current at the rated voltage, then the power factor at the terminal of the generator is
Which of the following option is/are correct for the Automatic Generation Control (AGC) and Automatic Voltage Regulator (AVR) installed with synchronous generators?
A three-phase synchronous motor with synchronous impedance of per unit per phase has a static stability limit of 2.5 per unit. The corresponding excitation voltage in per unit is ____ (Round off to 2 decimal places).
A star-connected 3-phase, 400 V, 50 kVA, 50 Hz synchronous motor has a synchronous reactance of 1 ohm per phase with negligible armature resistance. The shaft load on the motor is 10 kW while the power factor is 0.8 leading. The loss in the motor is 2 kW. The magnitude of the per phase excitation emf of the motor, in volts, is __________. (round off to nearest integer).
An alternator with internal voltage of and synchronous reactance of is connected by a transmission line of reactance to a synchronous motor having synchronous reactance and internal voltage of . If the real power supplied by the alternator is , then is _________ degrees. (Round off to 2 decimal places.) (Machines are of non-salient type. Neglect resistances.)
Consider the table given:
The correct combination that relates the constructional feature, machine type and mitigation is
A cylindrical rotor synchronous generator with constant real power output and constant terminal voltage is supplying 100 A current to a 0.9 lagging power factor load. An ideal reactor is now connected in parallel with the load, as a result of which the total lagging reactive power requirement of the load is twice the previous value while the real power remains unchanged. The armature current is now _______ A (rounded off to 2 decimal places).
A three-phase cylindrical rotor synchronous generator has a synchronous reactance and a negligible armature resistance. The magnitude of per phase terminal voltage is and the magnitude of per phase induced emf is . Considering the following two statements, P and Q. P : For any three-phase balanced leading load connected across the terminals of this synchronous generator, is always more than . Q : For any three-phase balanced lagging load connected across the terminals of this synchronous generator, is always less than . Which of the following options is correct?
A single 50 Hz synchronous generator on droop control was delivering 100 MW power to a system. Due to increase in load, generator power had to be increased by 10 MW. as a result of which, system frequency dropped to 49.75 Hz. Further increase in load in the system resulted in a frequency of 49.25 Hz. At this condition, the power in MW supplied by the generator is ________ (rounded off to 2 decimal places)
A cylindrical rotor synchronous generator has steady state synchronous reactance of 0.7 pu and subtransient reactance of 0.2 pu. It is operating at (1+j0) pu terminal voltage with an internal emf of (1+j0.7) pu. Following a three-phase solid short circuit fault at the terminal of the generator, the magnitude of the subtransient internal emf (rounded off to 2 decimal places) is ________ pu.
A 220 V (line), three-phase, Y-connected, synchronous motor has a synchronous impedance of (0.25+j2.5) /phase. The motor draws the rated current of 10 A at 0.8 pf leading. The rms value of line-to-line internal voltage in volts (round off to two decimal places) is __________.
A three-phase synchronous motor draws 200 A from the line at unity power factor at rated load. Considering the same line voltage and load, the line current at a power factor of 0.5 leading is
In a salient pole synchronous motor, the developed reluctance torque attains the maximum value when the load angle in electrical degrees is
A 25 kVA, 400 V, -connected, 3-phase, cylindrical rotor synchronous generator requires a field current of 5A to maintain the rated armature current under short-circuit condition. For the same field current, the open-circuit voltage is 360 V. Neglecting the armature resistance and magnetic saturation, its voltage regulation (in % with respect to terminal voltage), when the generator delivers the rated load at 0.8 pf leading, at rated terminal voltage is _________.
A three-phase, 50Hz, star-connected cylindrical-rotor synchronous machine is running as a motor. The machine is operated from a 6.6 kV grid and draws current at unity power factor (UPF). The synchronous reactance of the motor is 30 per phase. The load angle is . The power delivered to the motor in kW is _______.
A 3-phase 50 Hz generator supplies power of 3MW at 17.32 kV to a balanced 3-phase inductive load through an overhead line. The per phase line resistance and reactance are 0.25 and 3.925 respectively. If the voltage at the generator terminal is 17.87 kV, the power factor of the load is ________
If a synchronous motor is running at a leading power factor, its excitation induced voltage ( ) is
Two parallel connected, three-phase, 50Hz, 11kV, star-connected synchronous machines A and B, are operating as synchronous condensers. They together supply 50 MVAR to a 11 kV grid. Current supplied by both the machines are equal. Synchronous reactances of machine A and machine B are 1 and 3 respectively. Assuming the magnetic circuit to be linear, the ratio of excitation current of machine A to that of machine B is ________.

Want unlimited AI-generated Synchronous Machines questions?
Sign up free and practice with adaptive difficulty — Easy, Medium, Hard. New questions every session.
Start practising for free →